DRC-5V10W1AZ
Output Voltage: 5V
Output Power: 7.5W
Output Current: 1.5A
Input Voltage Range: 90-264Vac
Dimensions (H x W x D): 91 x 18 x 55.6 mm
Unit Weight: 0.06 kg (0.13 lb)
Highlights & Features
- Class II, Double Isolation (No Earth connection is required)
- Universal AC input voltage range and full power up to 55°C
- Power will not de-rate for the entire input voltage range
- Efficiency > 77.0% @ 115 Vac
- Can be installed in compact cabinets
- NEC Class 2 and Limited Power Source (LPS) approvals
- Conforms to harmonic current IEC/EN 61000-3-2, Class A
- Safety approval according to IEC/EN/UL 60950-1, IEC/EN/UL 62368-1 and UL 508
Output Current: 1.5A |
Output Voltage: 5V |
Output Power: 7.5W |
Line Regulation: < 1.0% (@ 90-264Vac input, 100% load) |
Load Regulation: < 2.0% (@ 90-264Vac input, 0-100% load) |
PARD: < 100mVpp |
Start-up Time: < 3,000ms @ nominal input (100% load) |
Hold-up Time: > 10ms @ 115Vac, > 60ms @ 230Vac (100% load) |
Dynamic Response (Overshoot & Undershoot O/P Voltage): ± 5% @ 90-264Vac input, 10-100% load |
Start-up with Capacitive Loads: 3,000μF Max |
Rise Time: < 70ms @ nominal input (100% load) |
Nominal Input Voltage: 100-240Vac |
Input Voltage Range: 90-264Vac |
Nominal Input Frequency: 50-60Hz |
Input Frequency Range: 47-63Hz |
DC Input Voltage Range: 125-375Vdc |
Input Current: < 0.3A @ 115Vac, < 0.2A @ 230Vac |
Efficiency at 100% load: > 77% @ 115Vac, > 76% @ 230Vac |
Inrush Current: < 15A @ 115Vac, < 30A @ 230Vac |
Leakage Current: < 0.25mA @ 240Vac |
Power Dissipation: 0% load: < 0.15W @ 115Vac & 230Vac, 100% load: < 2.24W @ 115Vac, < 2.35W @ 230Vac |
Case Chassis / Cover: Plastic |
|
Indicator: Green LED (DC OK) |
|
Cooling System: Convection |
|
Input Terminal: M4 x 2 Pins (Rated 300V/16A) |
|
Output Terminal: M4 x 2 Pins (Rated 300V/16A) |
|
Noise Sound Pressure Level (SPL): < 25dBA |
|
Mounting Rail: Standard TS35 DIN Rail in accordance with EN 60715 |
|
Wire: Input / Output: AWG 24-12 |
|
Unit Weight: 0.06 kg (0.13 lb) Dimensions: 91 x 18 x 55.6 mm |
|
Vibration (Operating): IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/S² (2G peak); 10 min per cycle, 60 min for all X, Y, Z directions |
Shock Test (Operating): IEC 60068-2-27, Half Sine Wave: 4G for a duration of 22ms, 3 shocks for each 3 directions, 9 times in total |
Operating Temperature: -25°C to +71°C |
Storage Temperature: -25°C to +85°C |
Power De-rating: > 55°C de-rate power by 2.5% / °C |
Operating Humidity: 5 to 95% RH (Non-Condensing) |
Operating Altitude: 0 to 2,000 Meters (6,560 ft.) |
Pollution Degree: 2 |
Over Voltage Category: II |
MTBF: > 500,000 hrs. as per Telcordia SR-332 (I/P: 100Vac, O/P: 100% load, Ta: 35°C) |
Expected Cap Life Time: 10 years (115Vac & 230Vac, 50% load @ 40°C) |
Emission: (CE & RE) Generic Standards: CISPR 32, EN/BS EN 55032, FCC Title 47: Class B |
Immunity: Generic Standards: EN/BS EN 55024 |
Harmonic Current Emissions: IEC/EN/BS EN 61000-3-2, Class A |
Voltage Fluctuation and Flicker: IEC/EN/BS EN 61000-3-3 |